CVE-2016-7112

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations.
Configurations

Configuration 1 (hide)

AND
cpe:2.3:a:siemens:en100_ethernet_module_firmware:*:*:*:*:*:*:*:*
cpe:2.3:h:siemens:en100_ethernet_module:-:*:*:*:*:*:*:*

History

No history.

Information

Published : 2016-09-06 00:59

Updated : 2023-12-10 11:46


NVD link : CVE-2016-7112

Mitre link : CVE-2016-7112

CVE.ORG link : CVE-2016-7112


JSON object : View

Products Affected

siemens

  • en100_ethernet_module_firmware
  • en100_ethernet_module
CWE
CWE-287

Improper Authentication