CVE-2018-13815

A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.
References
Configurations

Configuration 1 (hide)

AND
cpe:2.3:o:siemens:simatic_s7-1200_firmware:-:*:*:*:*:*:*:*
cpe:2.3:h:siemens:simatic_s7-1200:-:*:*:*:*:*:*:*

Configuration 2 (hide)

AND
cpe:2.3:o:siemens:simatic_s7-1500_firmware:*:*:*:*:*:*:*:*
cpe:2.3:h:siemens:simatic_s7-1500:-:*:*:*:*:*:*:*

History

No history.

Information

Published : 2018-12-13 16:29

Updated : 2023-12-10 12:44


NVD link : CVE-2018-13815

Mitre link : CVE-2018-13815

CVE.ORG link : CVE-2018-13815


JSON object : View

Products Affected

siemens

  • simatic_s7-1200
  • simatic_s7-1500
  • simatic_s7-1200_firmware
  • simatic_s7-1500_firmware
CWE
CWE-400

Uncontrolled Resource Consumption

CWE-410

Insufficient Resource Pool