CVE-2019-10919

A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Attackers with access to port 10005/tcp could perform device reconfigurations and obtain project files from the devices. The system manual recommends to protect access to this port. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
Link Resource
http://packetstormsecurity.com/files/153123/Siemens-LOGO-8-Missing-Authentication.html Exploit Third Party Advisory VDB Entry
http://seclists.org/fulldisclosure/2019/May/45 Exploit Mailing List Third Party Advisory
http://www.securityfocus.com/bid/108382 Third Party Advisory VDB Entry
https://cert-portal.siemens.com/productcert/pdf/ssa-542701.pdf Vendor Advisory
https://seclists.org/bugtraq/2019/May/73 Exploit Mailing List Third Party Advisory
Configurations

Configuration 1 (hide)

AND
cpe:2.3:o:siemens:logo\!8_bm_firmware:*:*:*:*:*:*:*:*
cpe:2.3:h:siemens:logo\!8_bm:*:*:*:*:*:*:*:*

History

No history.

Information

Published : 2019-05-14 20:29

Updated : 2023-12-10 12:59


NVD link : CVE-2019-10919

Mitre link : CVE-2019-10919

CVE.ORG link : CVE-2019-10919


JSON object : View

Products Affected

siemens

  • logo\!8_bm_firmware
  • logo\!8_bm
CWE
CWE-306

Missing Authentication for Critical Function