CVE-2019-6830 1 Schneider-electric 2 Modicon M580, Modicon M580 Firmware 2023-12-10 7.1 HIGH 5.9 MEDIUM
A CWE-248: Uncaught Exception vulnerability exists IN Modicon M580 all versions prior to V2.80, which could cause a possible denial of service when sending an appropriately timed HTTP request to the controller.
CVE-2019-6825 1 Schneider-electric 1 Proclima 2023-12-10 6.8 MEDIUM 7.8 HIGH
A CWE-427: Uncontrolled Search Path Element vulnerability exists in ProClima (all versions prior to version 8.0.0) which could allow a malicious DLL file, with the same name of any resident DLLs inside the software installation, to execute arbitrary code in all versions of ProClima prior to version 8.0.0.
CVE-2018-7844 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
A CWE-200: Information Exposure vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause the disclosure of SNMP information when reading memory blocks from the controller over Modbus.
CVE-2018-7852 1 Schneider-electric 8 Modicon M340, Modicon M340 Firmware, Modicon M580 and 5 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
A CWE-248: Uncaught Exception vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause denial of service when an invalid private command parameter is sent to the controller over Modbus.
CVE-2018-7821 1 Schneider-electric 3 Modicon M221, Modicon M221 Firmware, Somachine Basic 2023-12-10 5.0 MEDIUM 7.5 HIGH
An Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause cycle time impact when flooding the M221 ethernet interface while the Ethernet/IP adapter is activated.
CVE-2018-7820 1 Schneider-electric 8 Ap9630, Ap9630 Firmware, Ap9631 and 5 more 2023-12-10 5.0 MEDIUM 9.8 CRITICAL
A Credentials Management CWE-255 vulnerability exists in the APC UPS Network Management Card 2 AOS v6.5.6, which could cause Remote Monitoring Credentials to be viewed in plaintext when Remote Monitoring is enabled, and then disabled.
CVE-2018-7837 1 Schneider-electric 1 Iiot Monior 2023-12-10 5.0 MEDIUM 7.5 HIGH
An Improper Restriction of XML External Entity Reference ('XXE') vulnerability exists on numerous methods of the IIoT Monitor 3.1.38 software that could allow the software to resolve documents outside of the intended sphere of control, causing the software to embed incorrect documents into its output and expose restricted information.
CVE-2018-7817 1 Schneider-electric 1 Zelio Soft 2 2023-12-10 6.8 MEDIUM 7.8 HIGH
A Use After Free (CWE-416) vulnerability exists in Zelio Soft 2 v5.1 and prior versions which could cause remote code execution when opening a specially crafted Zelio Soft project file.
CVE-2018-7810 1 Schneider-electric 8 Modicom Bmxnor0200h, Modicom Bmxnor0200h Firmware, Modicom M340 and 5 more 2023-12-10 4.3 MEDIUM 6.1 MEDIUM
An Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 allowing an attacker to craft a URL containing JavaScript that will be executed within the user's browser, potentially impacting the machine the browser is running on.
CVE-2018-7799 1 Schneider-electric 1 Software Update Utility 2023-12-10 9.3 HIGH 7.8 HIGH
A DLL hijacking vulnerability exists in Schneider Electric Software Update (SESU), all versions prior to V2.2.0, which could allow an attacker to execute arbitrary code on the targeted system when placing a specific DLL file.
CVE-2018-7789 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2023-12-10 7.8 HIGH 7.5 HIGH
An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames.
CVE-2018-7830 1 Schneider-electric 8 Modicom Bmxnor0200h, Modicom Bmxnor0200h Firmware, Modicom M340 and 5 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
Improper Neutralization of CRLF Sequences in HTTP Headers ('HTTP Response Splitting') vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 where a denial of service can occur for ~1 minute by sending a specially crafted HTTP request.
CVE-2018-7797 1 Schneider-electric 3 Ecostruxure Energy Expert, Ecostruxure Power Monitoring Expert, Ecostruxure Power Scada Operation 2023-12-10 5.8 MEDIUM 6.1 MEDIUM
A URL redirection vulnerability exists in Power Monitoring Expert, Energy Expert (formerly Power Manager) - EcoStruxure Power Monitoring Expert (PME) v8.2 (all editions), EcoStruxure Energy Expert 1.3 (formerly Power Manager), EcoStruxure Power SCADA Operation (PSO) 8.2 Advanced Reports and Dashboards Module, EcoStruxure Power Monitoring Expert (PME) v9.0, EcoStruxure Energy Expert v2.0, and EcoStruxure Power SCADA Operation (PSO) 9.0 Advanced Reports and Dashboards Module which could cause a phishing attack when redirected to a malicious site.
CVE-2018-7815 1 Schneider-electric 1 Guicon 2023-12-10 6.8 MEDIUM 7.8 HIGH
A Type Confusion (CWE-843) vulnerability exists in Eurotherm by Schneider Electric GUIcon V2.0 (Gold Build 683.0) on c3core.dll which could cause remote code to be executed when parsing a GD1 file
CVE-2018-7790 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2023-12-10 7.5 HIGH 9.8 CRITICAL
An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC.
CVE-2018-7812 1 Schneider-electric 8 Modicom Bmxnor0200h, Modicom Bmxnor0200h Firmware, Modicom M340 and 5 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
An Information Exposure through Discrepancy vulnerability exists in the embedded web servers in all Modicon M340, Premium, Quantum PLCs and BMXNOR0200 where the web server sends different responses in a way that exposes security-relevant information about the state of the product, such as whether a particular operation was successful or not.
CVE-2018-7801 1 Schneider-electric 2 Evlink Parking, Evlink Parking Firmware 2023-12-10 6.8 MEDIUM 8.8 HIGH
A Code Injection vulnerability exists in EVLink Parking, v3.2.0-12_v1 and earlier, which could enable access with maximum privileges when a remote code execution is performed.
CVE-2018-7791 1 Schneider-electric 2 Modicon M221, Modicon M221 Firmware 2023-12-10 7.5 HIGH 9.8 CRITICAL
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to overwrite the original password with their password. If an attacker exploits this vulnerability and overwrite the password, the attacker can upload the original program from the PLC.
CVE-2018-7800 1 Schneider-electric 2 Evlink Parking, Evlink Parking Firmware 2023-12-10 10.0 HIGH 9.8 CRITICAL
A Hard-coded Credentials vulnerability exists in EVLink Parking, v3.2.0-12_v1 and earlier, which could enable an attacker to gain access to the device.
CVE-2018-7839 1 Schneider-electric 1 Iiot Monitor 2023-12-10 2.1 LOW 5.5 MEDIUM
A Cryptographic Issue (CWE-310) vulnerability exists in IIoT Monitor 3.1.38 which could allow information disclosure.