Vulnerabilities (CVE)

Filtered by vendor Siemens Subscribe
Total 1751 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2020-10041 1 Siemens 6 Sicam Mmu, Sicam Mmu Firmware, Sicam Sgu and 3 more 2023-12-10 4.3 MEDIUM 6.1 MEDIUM
A vulnerability has been identified in SICAM MMU (All versions < V2.05), SICAM SGU (All versions), SICAM T (All versions < V2.18). A stored Cross-Site-Scripting (XSS) vulnerability is present in different locations of the web application. An attacker might be able to take over a session of a legitimate user.
CVE-2020-12762 5 Canonical, Debian, Fedoraproject and 2 more 5 Ubuntu Linux, Debian Linux, Fedora and 2 more 2023-12-10 6.8 MEDIUM 7.8 HIGH
json-c through 0.14 has an integer overflow and out-of-bounds write via a large JSON file, as demonstrated by printbuf_memappend.
CVE-2020-15785 1 Siemens 1 Siveillance Video Client 2023-12-10 4.3 MEDIUM 5.3 MEDIUM
A vulnerability has been identified in Siveillance Video Client (All versions). In environments where Windows NTLM authentication is enabled the affected client application transmits usernames to the server in cleartext. This could allow an attacker in a privileged network position to obtain valid adminstrator login names and use this information to launch further attacks.
CVE-2019-10939 1 Siemens 10 Tim 3v-ie, Tim 3v-ie Advanced, Tim 3v-ie Advanced Firmware and 7 more 2023-12-10 6.8 MEDIUM 9.8 CRITICAL
A vulnerability has been identified in TIM 3V-IE (incl. SIPLUS NET variants) (All versions < V2.8), TIM 3V-IE Advanced (incl. SIPLUS NET variants) (All versions < V2.8), TIM 3V-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.3), TIM 4R-IE (incl. SIPLUS NET variants) (All versions < V2.8), TIM 4R-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.3). The affected versions contain an open debug port that is available under certain specific conditions. The vulnerability is only available if the IP address is configured to 192.168.1.2. If available, the debug port could be exploited by an attacker with network access to the device. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.
CVE-2020-7592 1 Siemens 9 Simatic Hmi Basic Panels 1st Generation, Simatic Hmi Basic Panels 2nd Generation, Simatic Hmi Comfort Panels and 6 more 2023-12-10 3.3 LOW 6.5 MEDIUM
A vulnerability has been identified in SIMATIC HMI Basic Panels 1st Generation (incl. SIPLUS variants) (All versions), SIMATIC HMI Basic Panels 2nd Generation (incl. SIPLUS variants) (All versions), SIMATIC HMI Comfort Panels (incl. SIPLUS variants) (All versions), SIMATIC HMI KTP700F Mobile Arctic (All versions), SIMATIC HMI Mobile Panels 2nd Generation (All versions), SIMATIC WinCC Runtime Advanced (All versions). Unencrypted communication between the configuration software and the respective device could allow an attacker to capture potential plain text communication and have access to sensitive information.
CVE-2019-20788 4 Canonical, Debian, Libvnc Project and 1 more 15 Ubuntu Linux, Debian Linux, Libvncserver and 12 more 2023-12-10 7.5 HIGH 9.8 CRITICAL
libvncclient/cursor.c in LibVNCServer through 0.9.12 has a HandleCursorShape integer overflow and heap-based buffer overflow via a large height or width value. NOTE: this may overlap CVE-2019-15690.
CVE-2020-14397 5 Canonical, Debian, Libvnc Project and 2 more 16 Ubuntu Linux, Debian Linux, Libvncserver and 13 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
An issue was discovered in LibVNCServer before 0.9.13. libvncserver/rfbregion.c has a NULL pointer dereference.
CVE-2020-10040 1 Siemens 6 Sicam Mmu, Sicam Mmu Firmware, Sicam Sgu and 3 more 2023-12-10 2.1 LOW 5.5 MEDIUM
A vulnerability has been identified in SICAM MMU (All versions < V2.05), SICAM SGU (All versions), SICAM T (All versions < V2.18). An attacker with local access to the device might be able to retrieve some passwords in clear text.
CVE-2020-15791 1 Siemens 28 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 312 Firmware, Simatic S7-300 Cpu 314 and 25 more 2023-12-10 3.3 LOW 6.5 MEDIUM
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 CPU family (incl. SIPLUS variants) (All versions), SIMATIC WinAC RTX (F) 2010 (All versions), SINUMERIK 840D sl (All versions). The authentication protocol between a client and a PLC via port 102/tcp (ISO-TSAP) insufficiently protects the transmitted password. This could allow an attacker that is able to intercept the network traffic to obtain valid PLC credentials.
CVE-2020-7589 1 Siemens 2 Logo\! 8 Bm, Logo\! 8 Bm Firmware 2023-12-10 6.4 MEDIUM 9.1 CRITICAL
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions). The vulnerability could lead to an attacker reading and modifying the device configuration and obtain project files from affected devices. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 135/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2020-7588 1 Siemens 13 Opcenter Execution Discrete, Opcenter Execution Foundation, Opcenter Execution Process and 10 more 2023-12-10 5.0 MEDIUM 5.3 MEDIUM
A vulnerability has been identified in Opcenter Execution Discrete (All versions < V3.2), Opcenter Execution Foundation (All versions < V3.2), Opcenter Execution Process (All versions < V3.2), Opcenter Intelligence (All versions < V3.3), Opcenter Quality (All versions < V11.3), Opcenter RD&L (V8.0), SIMATIC IT LMS (All versions < V2.6), SIMATIC IT Production Suite (All versions < V8.0), SIMATIC Notifier Server for Windows (All versions), SIMATIC PCS neo (All versions < V3.0 SP1), SIMATIC STEP 7 (TIA Portal) V15 (All versions < V15.1 Update 5), SIMATIC STEP 7 (TIA Portal) V16 (All versions < V16 Update 2), SIMOCODE ES V15.1 (All versions < V15.1 Update 4), SIMOCODE ES V16 (All versions < V16 Update 1), Soft Starter ES V15.1 (All versions < V15.1 Update 3), Soft Starter ES V16 (All versions < V16 Update 1). Sending a specially crafted packet to the affected service could cause a partial remote denial-of-service, that would cause the service to restart itself.
CVE-2020-10045 1 Siemens 6 Sicam Mmu, Sicam Mmu Firmware, Sicam Sgu and 3 more 2023-12-10 6.8 MEDIUM 8.8 HIGH
A vulnerability has been identified in SICAM MMU (All versions < V2.05), SICAM SGU (All versions), SICAM T (All versions < V2.18). An error in the challenge-response procedure could allow an attacker to replay authentication traffic and gain access to protected areas of the web application.
CVE-2018-21247 5 Canonical, Debian, Libvnc Project and 2 more 16 Ubuntu Linux, Debian Linux, Libvncserver and 13 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
An issue was discovered in LibVNCServer before 0.9.13. There is an information leak (of uninitialized memory contents) in the libvncclient/rfbproto.c ConnectToRFBRepeater function.
CVE-2020-11655 7 Canonical, Debian, Netapp and 4 more 18 Ubuntu Linux, Debian Linux, Ontap Select Deploy Administration Utility and 15 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
SQLite through 3.31.1 allows attackers to cause a denial of service (segmentation fault) via a malformed window-function query because the AggInfo object's initialization is mishandled.
CVE-2020-10037 1 Siemens 6 Sicam Mmu, Sicam Mmu Firmware, Sicam Sgu and 3 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in SICAM MMU (All versions < V2.05), SICAM SGU (All versions), SICAM T (All versions < V2.18). By performing a flooding attack against the web server, an attacker might be able to gain read access to the device's memory, possibly revealing confidential information.
CVE-2020-7583 1 Siemens 1 Automation License Manager 2023-12-10 4.6 MEDIUM 7.8 HIGH
A vulnerability has been identified in Automation License Manager 5 (All versions), Automation License Manager 6 (All versions < V6.0.8). The application does not properly validate the users' privileges when executing some operations, which could allow a user with low permissions to arbitrary modify files that should be protected against writing.
CVE-2020-14401 4 Debian, Libvncserver Project, Opensuse and 1 more 15 Debian Linux, Libvncserver, Leap and 12 more 2023-12-10 6.4 MEDIUM 6.5 MEDIUM
An issue was discovered in LibVNCServer before 0.9.13. libvncserver/scale.c has a pixel_value integer overflow.
CVE-2019-19300 1 Siemens 65 Ktk Ate530s, Ktk Ate530s Firmware, Sidoor Atd430w and 62 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200 (All versions), Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P (All versions), KTK ATE530S (All versions), SIDOOR ATD430W (All versions), SIDOOR ATE530S COATED (All versions), SIDOOR ATE531S (All versions), SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions < V2.0), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V2.0), SIMATIC ET200AL IM157-1 PN (All versions), SIMATIC ET200ecoPN, AI 8xRTD/TC, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, CM 4x IO-Link, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, CM 8x IO-Link, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, CM 8x IO-Link, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DI 16x24VDC, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DI 8x24VDC, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DIQ 16x24VDC/2A, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DQ 8x24VDC/0,5A, M12-L (All versions >= V5.1.1), SIMATIC ET200ecoPN, DQ 8x24VDC/2A, M12-L (All versions >= V5.1.1), SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants) (All versions >= V4.2), SIMATIC ET200SP IM155-6 MF HF (All versions), SIMATIC ET200SP IM155-6 PN HA (incl. SIPLUS variants) (All versions), SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants) (All versions >= V4.2), SIMATIC ET200SP IM155-6 PN/2 HF (incl. SIPLUS variants) (All versions >= V4.2), SIMATIC ET200SP IM155-6 PN/3 HF (incl. SIPLUS variants) (All versions >= V4.2), SIMATIC MICRO-DRIVE PDC (All versions), SIMATIC PN/MF Coupler (All versions), SIMATIC PN/PN Coupler (All versions >= V4.2), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.0), SIMATIC S7-1500 Software Controller (All versions < V2.0), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions), SIMATIC S7-300 CPU 315-2 PN/DP (All versions), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions), SIMATIC S7-300 CPU 317-2 PN/DP (All versions), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions), SIMATIC S7-300 CPU 319-3 PN/DP (All versions), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions), SIMATIC S7-400 H V6 CPU family and below (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions), SIMATIC TDC CP51M1 (All versions), SIMATIC TDC CPU555 (All versions), SIMATIC WinAC RTX 2010 (All versions), SIMATIC WinAC RTX F 2010 (All versions), SINAMICS S/G Control Unit w. PROFINET (All versions), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions), SIPLUS NET PN/PN Coupler (All versions >= V4.2), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions), SIPLUS S7-300 CPU 315-2 PN/DP (All versions), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions), SIPLUS S7-300 CPU 317-2 PN/DP (All versions), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions). The Interniche-based TCP Stack can be forced to make very expensive calls for every incoming packet which can lead to a denial of service.
CVE-2020-10050 1 Siemens 1 Simatic Rtls Locating Manager 2023-12-10 7.2 HIGH 7.8 HIGH
A vulnerability has been identified in SIMATIC RTLS Locating Manager (All versions < V2.10.2). The directory of service executables of the affected application could allow a local attacker to include arbitrary commands that are executed with SYSTEM privileges when the system restarts.
CVE-2020-10055 1 Siemens 2 Desigo Consumption Control, Desigo Consumption Control Compact 2023-12-10 9.3 HIGH 9.8 CRITICAL
A vulnerability has been identified in Desigo CC (V4.x), Desigo CC (V3.x), Desigo CC Compact (V4.x), Desigo CC Compact (V3.x). Affected applications are delivered with a 3rd party component (BIRT) that contains a remote code execution vulnerability if the Advanced Reporting Engine is enabled. The vulnerability could allow a remote unauthenticated attacker to execute arbitrary commands on the server with SYSTEM privileges.