Vulnerabilities (CVE)

Filtered by vendor Carel Subscribe
Total 11 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2023-3643 1 Carel 2 Boss Mini, Boss Mini Firmware 2024-04-11 7.5 HIGH 9.8 CRITICAL
A vulnerability was found in Boss Mini 1.4.0 Build 6221. It has been classified as critical. This affects an unknown part of the file boss/servlet/document. The manipulation of the argument path leads to file inclusion. It is possible to initiate the attack remotely. The exploit has been disclosed to the public and may be used. The identifier VDB-233889 was assigned to this vulnerability.
CVE-2022-34827 1 Carel 2 Boss Mini, Boss Mini Firmware 2023-12-10 N/A 9.9 CRITICAL
Carel Boss Mini 1.5.0 has Improper Access Control.
CVE-2020-18329 1 Carel 3 Pcoweb Card Bios, Pcoweb Card Boot, Pcoweb Card Web 2023-12-10 N/A 7.5 HIGH
An issue was discovered in Rehau devices that use a pCOWeb card BIOS v6.27, BOOT v5.00, web version v2.2, allows attackers to gain full unauthenticated access to the configuration and service interface.
CVE-2022-37122 1 Carel 4 Applica, Pcoweb Card, Pcoweb Card Firmware and 1 more 2023-12-10 N/A 7.5 HIGH
Carel pCOWeb HVAC BACnet Gateway 2.1.0, Firmware: A2.1.0 - B2.1.0, Application Software: 2.15.4A Software v16 13020200 suffers from an unauthenticated arbitrary file disclosure vulnerability. Input passed through the 'file' GET parameter through the 'logdownload.cgi' Bash script is not properly verified before being used to download log files. This can be exploited to disclose the contents of arbitrary and sensitive files via directory traversal attacks.
CVE-2019-13553 2 Carel, Rittal 2 Pcoweb Firmware, Chiller Sk 3232 2023-12-10 10.0 HIGH 9.8 CRITICAL
Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems is configured using hard-coded credentials. These credentials could allow attackers to influence the primary operations of the affected systems, namely turning the cooling unit on and off and setting the temperature set point.
CVE-2019-13549 2 Carel, Rittal 2 Pcoweb Firmware, Chiller Sk 3232 2023-12-10 5.0 MEDIUM 7.5 HIGH
Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems does not provide a sufficient level of protection against unauthorized configuration changes. Primary operations, namely turning the cooling unit on and off and setting the temperature set point, can be modified without authentication.
CVE-2019-11369 1 Carel 2 Pcoweb Card, Pcoweb Card Firmware 2023-12-10 4.0 MEDIUM 8.8 HIGH
An issue was discovered in Carel pCOWeb prior to B1.2.4. In /config/pw_changeusers.html the device stores cleartext passwords, which may allow sensitive information to be read by someone with access to the device.
CVE-2019-11370 1 Carel 2 Pcoweb Card, Pcoweb Card Firmware 2023-12-10 3.5 LOW 5.4 MEDIUM
Stored XSS was discovered in Carel pCOWeb prior to B1.2.4, as demonstrated by the config/pw_snmp.html "System contact" field.
CVE-2019-9484 1 Carel 2 Pcoweb Card, Pcoweb Card Firmware 2023-12-10 5.0 MEDIUM 7.5 HIGH
The Glen Dimplex Deutschland GmbH implementation of the Carel pCOWeb configuration tool allows remote attackers to obtain access via an HTTP session on port 10000, as demonstrated by reading the modem password (which is 1234), or reconfiguring "party mode" or "vacation mode."
CVE-2016-0867 1 Carel 1 Plantvisor Enhanced 2023-12-10 7.8 HIGH 7.5 HIGH
CAREL PlantVisorEnhanced allows remote attackers to bypass intended access restrictions via a direct file request.
CVE-2011-3487 1 Carel 1 Plantvisor 2023-12-10 5.0 MEDIUM N/A
Directory traversal vulnerability in CarelDataServer.exe in Carel PlantVisor 2.4.4 and earlier allows remote attackers to read arbitrary files via a .. (dot dot) in an HTTP GET request.