CVE-2023-3243 1 Honeywell 2 Alerton Bcm-web, Alerton Bcm-web Firmware 2024-04-25 N/A 9.8 CRITICAL
** UNSUPPORTED WHEN ASSIGNED ** [An attacker can capture an authenticating hash and utilize it to create new sessions. The hash is also a poorly salted MD5 hash, which could result in a successful brute force password attack. Impacted product is BCM-WEB version 3.3.X. Recommended fix: Upgrade to a supported product such as Alerton ACM.] Out of an abundance of caution, this CVE ID is being assigned to better serve our customers and ensure all who are still running this product understand that the product is end of life and should be removed or upgraded. 
CVE-2023-26597 1 Honeywell 2 C300, C300 Firmware 2024-04-22 N/A 7.5 HIGH
Controller DoS due to buffer overflow in the handling of a specially crafted message received by the controller. See Honeywell Security Notification for recommendations on upgrading and versioning. See Honeywell Security Notification for recommendations on upgrading and versioning.
CVE-2023-25948 1 Honeywell 4 Direct Station, Engineering Station, Experion Server and 1 more 2024-04-22 N/A 7.5 HIGH
Server information leak of configuration data when an error is generated in response to a specially crafted message. See Honeywell Security Notification for recommendations on upgrading and versioning.
CVE-2023-25770 1 Honeywell 2 C300, C300 Firmware 2024-04-22 N/A 7.5 HIGH
Controller DoS may occur due to buffer overflow when an error is generated in response to a specially crafted message. See Honeywell Security Notification for recommendations on upgrading and versioning.
CVE-2023-25178 1 Honeywell 2 C300, C300 Firmware 2024-04-22 N/A 9.8 CRITICAL
Controller may be loaded with malicious firmware which could enable remote code execution. See Honeywell Security Notification for recommendations on upgrading and versioning.
CVE-2023-25078 1 Honeywell 4 Direct Station, Engineering Station, Experion Server and 1 more 2024-04-22 N/A 7.5 HIGH
Server or Console Station DoS due to heap overflow occurring during the handling of a specially crafted message for a specific configuration operation.  See Honeywell Security Notification for recommendations on upgrading and versioning.
CVE-2023-24480 1 Honeywell 2 C300, C300 Firmware 2024-04-22 N/A 7.5 HIGH
Controller DoS due to stack overflow when decoding a message from the server.  See Honeywell Security Notification for recommendations on upgrading and versioning.
CVE-2023-23585 1 Honeywell 4 Direct Station, Engineering Station, Experion Server and 1 more 2024-04-22 N/A 7.5 HIGH
Experion server DoS due to heap overflow occurring during the handling of a specially crafted message for a specific configuration operation.  See Honeywell Security Notification for recommendations on upgrading and versioning.
CVE-2022-30320 1 Honeywell 1 Saia Pg5 Controls Suite 2024-02-14 N/A 4.3 MEDIUM
Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication is done by using the S-Bus 'write byte' message to a specific address and supplying a hashed version of the password. The hashing algorithm used is based on CRC-16 and as such not cryptographically secure. An insecure hashing algorithm is used. An attacker capable of passively observing traffic can intercept the hashed credentials and trivially find collisions allowing for authentication without having to bruteforce a keyspace defined by the actual strength of the password. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
CVE-2022-30317 1 Honeywell 2 Experion Lx, Experion Lx Firmware 2024-02-13 N/A 9.1 CRITICAL
Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.
CVE-2022-30313 1 Honeywell 2 Safety Manager, Safety Manager Firmware 2024-02-13 N/A 7.5 HIGH
Honeywell Experion PKS Safety Manager through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0051, there is a Honeywell Experion PKS Safety Manager multiple proprietary protocols with unauthenticated functionality issue. The affected components are characterized as: Honeywell Experion TCP (51000/TCP), Safety Builder (51010/TCP). The potential impact is: Manipulate controller state, Manipulate controller configuration, Manipulate controller logic, Manipulate controller files, Manipulate IO. The Honeywell Experion PKS Distributed Control System (DCS) Safety Manager utilizes several proprietary protocols for a wide variety of functionality, including process data acquisition, controller steering and configuration management. These protocols include: Experion TCP (51000/TCP) and Safety Builder (51010/TCP). None of these protocols have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocols in question. An attacker capable of invoking the protocols' functionalities could achieve a wide range of adverse impacts, including (but not limited to), the following: for Experion TCP (51000/TCP): Issue IO manipulation commands, Issue file read/write commands; and for Safety Builder (51010/TCP): Issue controller start/stop commands, Issue logic download/upload commands, Issue file read commands, Issue system time change commands. A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.
CVE-2022-30314 1 Honeywell 2 Safety Manager, Safety Manager Firmware 2024-02-13 N/A 4.6 MEDIUM
Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. The affected components are characterized as: POLO bootloader. The potential impact is: Manipulate firmware. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 serial interface for firmware management purposes. When booting, the Safety Manager exposes the Enea POLO bootloader via this interface. Access to the boot configuration is controlled by means of credentials hardcoded in the Safety Manager firmware. The credentials for the bootloader are hardcoded in the firmware. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize these credentials to control the boot process and manipulate the unauthenticated firmware image (see FSCT-2022-0054).
CVE-2022-30319 1 Honeywell 1 Saia Pg5 Controls Suite 2024-02-09 N/A 8.1 HIGH
Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
CVE-2023-5390 1 Honeywell 4 Controledge Unit Operations Controller, Controledge Unit Operations Controller Firmware, Controledge Virtual Unit Operations Controller and 1 more 2024-02-08 N/A 5.3 MEDIUM
An attacker could potentially exploit this vulnerability, leading to files being read from the Honeywell Experion ControlEdge VirtualUOC and ControlEdge UOC. This exploit could be used to read files from the controller that may expose limited information from the device. Honeywell recommends updating to the most recent version of the product. See Honeywell Security Notification for recommendations on upgrading and versioning.
CVE-2023-5389 1 Honeywell 4 Controledge Unit Operations Controller, Controledge Unit Operations Controller Firmware, Controledge Virtual Unit Operations Controller and 1 more 2024-02-08 N/A 7.5 HIGH
An attacker could potentially exploit this vulnerability, leading to the ability to modify files on Honeywell Experion ControlEdge VirtualUOC and ControlEdge UOC . This exploit could be used to write a file that may result in unexpected behavior based on configuration changes or updating of files that could result in subsequent execution of a malicious application if triggered. Honeywell recommends updating to the most recent version of the product. See Honeywell Security Notification for recommendations on upgrading and versioning. 
CVE-2023-6179 1 Honeywell 1 Prowatch 2023-12-10 N/A 7.8 HIGH
Honeywell ProWatch, 4.5, including all Service Pack versions, contain a Vulnerability in Application Server's executable folder(s). A(n) attacker could potentially exploit this vulnerability, leading to a standard user to have arbitrary system code execution. Honeywell recommends updating to the most recent version of this product, service or offering (Pro-watch 6.0.2, 6.0, 5.5.2,5.0.5).
CVE-2023-3712 1 Honeywell 2 Pm43, Pm43 Firmware 2023-12-10 N/A 7.8 HIGH
Files or Directories Accessible to External Parties vulnerability in Honeywell PM43 on 32 bit, ARM (Printer web page modules) allows Privilege Escalation.This issue affects PM43 versions prior to P10.19.050004.  Update to the latest available firmware version of the respective printers to version MR19.5 (e.g. P10.19.050006).
CVE-2023-24474 1 Honeywell 4 Direct Station, Engineering Station, Experion Server and 1 more 2023-12-10 N/A 7.5 HIGH
Experion server may experience a DoS due to a heap overflow which could occur when handling a specially crafted message
CVE-2023-22435 1 Honeywell 4 Direct Station, Engineering Station, Experion Server and 1 more 2023-12-10 N/A 7.5 HIGH
Experion server may experience a DoS due to a stack overflow when handling a specially crafted message.
CVE-2023-3711 1 Honeywell 2 Pm43, Pm43 Firmware 2023-12-10 N/A 8.8 HIGH
Session Fixation vulnerability in Honeywell PM43 on 32 bit, ARM (Printer web page modules) allows Session Credential Falsification through Prediction.This issue affects PM43 versions prior to P10.19.050004. Update to the latest available firmware version of the respective printers to version MR19.5 (e.g. P10.19.050006).