Vulnerabilities (CVE)

Filtered by vendor Siemens Subscribe
Filtered by product Nucleus Net
Total 25 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2021-25677 1 Siemens 6 Nucleus Net, Nucleus Readystart V3, Nucleus Readystart V4 and 3 more 2023-12-10 5.0 MEDIUM 5.3 MEDIUM
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), SIMOTICS CONNECT 400 (All versions >= V0.5.0.0 < V1.0.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS client does not properly randomize DNS transaction IDs. That could allow an attacker to poison the DNS cache or spoof DNS resolving.
CVE-2020-27009 1 Siemens 2 Nucleus Net, Nucleus Source Code 2023-12-10 6.8 MEDIUM 8.1 HIGH
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus Source Code (Versions including affected DNS modules), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name record decompression functionality does not properly validate the pointer offset values. The parsing of malformed responses could result in a write past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to execute code in the context of the current process or cause a denial-of-service condition.
CVE-2020-27736 1 Siemens 6 Nucleus Net, Nucleus Readystart V3, Nucleus Readystart V4 and 3 more 2023-12-10 5.8 MEDIUM 6.5 MEDIUM
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory.
CVE-2021-27393 1 Siemens 3 Nucleus Net, Nucleus Readystart V3, Nucleus Source Code 2023-12-10 5.0 MEDIUM 5.3 MEDIUM
A vulnerability has been identified in Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2013.08), Nucleus Source Code (Versions including affected DNS modules). The DNS client does not properly randomize UDP port numbers of DNS requests. That could allow an attacker to poison the DNS cache or spoof DNS resolving.
CVE-2020-28388 4 Arm, Mips, Powerpc Project and 1 more 8 Arm, Mips, Powerpc and 5 more 2023-12-10 5.0 MEDIUM 5.3 MEDIUM
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.