Vulnerabilities (CVE)

Filtered by vendor Siemens Subscribe
Filtered by product Simatic S7-400
Total 5 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2018-16557 1 Siemens 8 Simatic S7-400, Simatic S7-400 Firmware, Simatic S7-400 Pn\/dp V7 and 5 more 2023-12-10 7.8 HIGH 8.2 HIGH
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
CVE-2018-16556 1 Siemens 10 Simatic S7-400, Simatic S7-400 Firmware, Simatic S7-400 Pn\/dp V7 and 7 more 2023-12-10 7.8 HIGH 7.5 HIGH
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
CVE-2018-4850 1 Siemens 4 Simatic S7-400, Simatic S7-400 Firmware, Simatic S7-400h and 1 more 2023-12-10 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in SIMATIC S7-400 (incl. F) CPU hardware version 4.0 and below (All versions), SIMATIC S7-400 (incl. F) CPU hardware version 5.0 (All firmware versions < V5.2), SIMATIC S7-400H CPU hardware version 4.5 and below (All versions). The affected CPUs improperly validate S7 communication packets which could cause a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart.
CVE-2017-2681 1 Siemens 155 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 Pn Io and 152 more 2023-12-10 6.1 MEDIUM 6.5 MEDIUM
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. This vulnerability affects only SIMATIC HMI Multi Panels and HMI Mobile Panels, and S7-300/S7-400 devices.
CVE-2017-2680 1 Siemens 183 S110 Pn, Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware and 180 more 2023-12-10 6.1 MEDIUM 6.5 MEDIUM
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.