Vulnerabilities (CVE)

Filtered by vendor Siemens Subscribe
Filtered by product Sinetplan
Total 2 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2022-27194 1 Siemens 3 Simatic Pcs Neo, Sinetplan, Totally Integrated Automation Portal 2023-12-10 7.8 HIGH 7.5 HIGH
A vulnerability has been identified in SIMATIC PCS neo (Administration Console) (All versions < V3.1 SP1), SINETPLAN (All versions), TIA Portal (V15, V15.1, V16 and V17). The affected system cannot properly process specially crafted packets sent to port 8888/tcp. A remote attacker could exploit this vulnerability to cause a Denial-of-Service condition. The affected devices must be restarted manually.
CVE-2019-10915 1 Siemens 2 Sinetplan, Tia Administrator 2023-12-10 4.6 MEDIUM 7.8 HIGH
A vulnerability has been identified in TIA Administrator (All versions < V1.0 SP1 Upd1). The integrated configuration web application (TIA Administrator) allows to execute certain application commands without proper authentication. The vulnerability could be exploited by an attacker with local access to the affected system. Successful exploitation requires no privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.